Title: Increase in fault ride through capability of direct drive permanent magnet based wind farm using VSC-HVDC
Authors: Maleki, H. 
Ramachandaramurthy, V.K. 
Lak, M. 
Issue Date: 2013
Abstract: Burning of fossil fuels and green house gasses causes global warming. This has led to governments to explore the use of green energies instead of fossil fuels. The availability of wind has made wind technology a viable alternative for generating electrical power. Hence, many parts of the world, especially Europe are experiencing a growth in wind farms. However, by increasing the number of wind farms connected to the grid, power quality and voltage stability of grid becomes a matter of concern. In this paper, VSC-HVDC control strategy which enables the wind farm to ride-through faults and regulate voltage for fault types is proposed. The results show that the wind turbine output voltage fulfills the E.ON grid code requirements, when subjected to three phase to ground fault. Hence, continues operation of the wind farm is achieved. © Published under licence by IOP Publishing Ltd.
URI: http://dspace.uniten.edu.my/jspui/handle/123456789/7758
Appears in Collections:COE Scholarly Publication